Options for mA Output Process Variable (continued)Table 6-2:
Process variable
Label
Display ProLink III Field Communicator
Concentration measurement
Specific Gravity SG Specific Gravity Specific Gravity (CM)
Concentration CONC Concentration Concentration (CM)
Referred Density (Concen-
tration)
RDENS Referred Density (Concen-
tration)
Density at Reference (CM)
6.2.2 Configure Lower Range Value (LRV) and Upper Range Value
(URV)
Display OFF-LINE MAINT > OFF-LINE CONFG > IO > CONFIG MAO 1 > 4 mA
OFF-LINE MAINT > OFF-LINE CONFG > IO > CONFIG MAO 1 > 20 mA
OFF-LINE MAINT > OFF-LINE CONFG > IO > CH B > MAO 2 > CONFIG MAO 2 > 4 mA
OFF-LINE MAINT > OFF-LINE CONFG > IO > CH B > MAO 2 > CONFIG MAO 2 > 20 mA
ProLink III Device Tools > Configuration > I/O > Outputs > mA Output > mA Output 1 > Lower Range Value
Device Tools > Configuration > I/O > Outputs > mA Output > mA Output 1 > Upper Range Vaue
Device Tools > Configuration > I/O > Outputs > mA Output > mA Output 2 > Lower Range Value
Device Tools > Configuration > I/O > Outputs > mA Output > mA Output 2 > Upper Range Vaue
Field Communicator Configure > Manual Setup > Inputs/Outputs > mA Output 1 > mA Output Settings > PV LRV
Configure > Manual Setup > Inputs/Outputs > mA Output 1 > mA Output Settings > PV URV
Configure > Manual Setup > Inputs/Outputs > mA Output 2 > mA Output Settings > SV LRV
Configure > Manual Setup > Inputs/Outputs > mA Output 2 > mA Output Settings > SV URV
Overview
The Lower Range Value (LRV) and Upper Range Value (URV) are used to scale the mA output,
that is, to define the relationship between mA Output Process Variable and the mA output
level.
Important
Your device may have been ordered with predefined values for LRV and URV that are appropriate for
specific applications. However, you can change these settings if you want to.
Prerequisites
Ensure that mA Output Process Variable is set to the desired process variable. Each process
variable has its own set of LRV and URV values. When you change the values of LRV and
URV, you are configuring values for the currently assigned mA output process variable.
Integrate the meter with the control system
86 Micro Motion
®
Compact Density Meters (CDM)