6
Maintenance
and
Commissionin
g
6.1
Procedure
This maintenance schedule / commissioning procedure is intended for guidance only. The actual
level of maintenance required will depend on the severity of the operating environment and
the likelihood of damage or the rate of contamination from oil, sea spray, deluge system etc. It
is
advisable to regularly review maintenance reports and adapt the maintenance period to the
operating environment.
micro
p
ack.co.uk
FDS301 Flame Detector FDS301 Safety and Technical Manual
24
Ref: 2200.5009 Rev: 2.3 ECN 4434
Cautions:
Use only approved parts and accessories with this equipment.
Do not attempt to replace the window as the glass and the front cover are individually
matched pairs to meet the stringent requirement of the Hazardous area certification. The
threaded portions of the detector are flame paths. These threads and the flame paths around
the window are not to be repaired.
To maintain safety standards, commissioning and regular maintenance should be performed
by a qualified person.