8.4
Certification and A
pp
rovals
8.5
O
p
eratin
g
S
p
ecification
micro
p
ack.co.uk
Parameter Authority/Standard Approval Certificate
Hazardous Area Certification ATEX Ex II 2 G Ex db IIC T4 IP66 FM07ATEX0033
Hazardous Area Certification NEC 505 Class 1 Zone 1 A Ex db IIC T4 3035984
Hazardous Area Certification NEC 500 Class 1 Div 1 Groups B,C & D 3035984
Hazardous Area Certification IEC Ex Ex II 2 G Ex db IIC T4 IP66 FME 07 0002
Fire Service Listing FM Class 3260, 3600, 3615, 3800 3009845
CE Certification (Emissions) York EMC EN61000-6-3-201 9762TC2
CE Certification (immunity) York EMC EN50130-4+A1 1998+A2 2003 9762TC2
Functional Safety Exida IEC 61508:2000 Parts 1,2,3 SIL 2* MP 080203 C001
FDS301 Flame Detector FDS301 Safety and Technical Manual
32
Ref: 2200.5009 Rev: 2.3 ECN 4434
Parameter Units Min Max Comment
Detector Range (depth of field) m 2 44
Horizontal Field of View Degrees 90 -
Vertical Field of View Degrees - 65
Detector Response Time Seconds 4 30
Power on reset delay Seconds 5 30
Optical Verification - - - Default - Off