Parameter Units Min Max Comment
Operating Ambient Temperature °C - 60 + 85 T4
Storage Ambient Temperature °C - 60 + 85
Relative Humidity % RH 5 95
Non
Condensing
Parameter Units Value Comment
Enclosure
Overall Dimensions mm 100 Diameter x 200 Length
Shipping Weight Kg 2.5 6
Material
LM25 Alloy 316SS
Coating Colour Red Epoxy Coated Finish
Cable Entries mm/inches
M25, M20, ½ NPT, 3/4NPT 1 or 2 off
Terminal Wire Size mm
2
2.5
Ingress Protection IP 66
Mounting Bracket
Support Fixings mm 2 x M8
Vertical Adjustment Degrees 0 to 45
Horizontal Adjustment
Degrees
0
Provided by
support
Axial (horizontal) Rotation Degrees +/-45
FDS301 Flame Detector FDS301 Safety and Technical Manual
31