Aqua Tempo Super Series air cooled scroll chiller unit (50Hz) MCAC-ATSM-201606
15
Model
MC-SP25M-RN1L
MC-SP35M/RN1L
Cooling Capacity
kW
25
35
Heating Capacity
kW
26
38
Power input
Cooling
kW
9.2
12.7
Cooling rated current
A
14.8
20.4
Heating
kW
9.15
12.5
Heating rated current
A
15.2
20
EER
kW / kW
2.72
2.76
COP
kW / kW
2.84
3.04
Power supply
V/Ph/Hz
380-415/3/50
380-415/3/50
Power
supply
Manual switch
A
50
50
Fuse
A
36
36
Max. input consumption
kW
12.2
15.2
Rated current
A
24.0
32.1
Max. starting current
A
121.2
177
Compressor
Type
Scroll (fixed speed)
Scroll (fixed speed)
Brand
Danfoss
Danfoss
Model
HCJ106
SH140A4ALC
Quantity
Pieces
1
1
Capacity
kW
26.1
36.8
Input
kW
8.08
11.3
Rated load Amps(RLA)
A
14.3
21.4
Locked rotor Amp(LRA)
A
121.2
147
Refrigerant oil
ml
2460
3300
Refrigerant
Type
R410A
R410A
Refrigerant control
EXV+ capillary
EXV+ capillary
Weight
kg
3.1
5.4
Condenser
(Air side)
Type
Fin-coil
Fin-coil
Number of rows
1
2
Fan motor model
YDK550-6E
YDK550-6E
Quantity of fan motor
Pieces
1
1
Air flow
×10
3
m
3
/h
13.5
13.5
Fan motor rated current
A
3.7
3.7
Fan motor power input
kW
0.8
0.8
Evaporator
(Water side)
Type
Plate
Plate
Water pump power input
kW
1.2
1.2
Pump head
m
19
16
Volume
L
1.89
2.77
Water inlet/outlet pipeline
inside normal diameter
mm
DN40
DN40
Water flow
m
3
/h
4.3
6
Max. design pressure
MPa
1
1
Water pipe connection type
Flexible joint
Flexible joint
Dimension
Net(D×W)
mm
1020×177980
1020×177980
Packing size(D×W)
mm
1070×1901030
1070×1901030
Weight
Net weight
kg
313
343
Operation weight
kg
323
353
Connection
wiring
Power wire
mm
2
10×4+16×1
10×4+16×1
Signal wire
mm
2
0.75×3-core with shielding
0.75×3-core with shielding
Control type
Wired controller
Wired controller
Noise level
dB(A)
65
65
Safety protection device
1) Protection for over-high discharge pressure.
2) Protection for over-low suction pressure.
3) Power supply phase sequence protection.
4) Anti-freezing protection in cooling mode.

Table of Contents