MCAC-ATSM-201606 Aqua Tempo Super Series air cooled scroll chiller unit (50Hz)
16
5) Anti-freezing protection in Winter.
6) Protection for compressor over current.
7) Protection for compressor overload.
8) Outlet and inlet water temperature difference protection.
9) Compressor discharge temperature protection.
10) Water flow cut-off protection.
11) Sensor malfunction protection.
12) Low ambient temperature drive-up protection
13) Low temperature protection of shell and tube heat exchanger.
Cooling:5~17
Heating:25~50
Cooling:-10~46
Heating:-15~24
Note: Specifications are based on the following conditions:
Cooling : chilled water inlet/outlet: 12˚C / 7˚C, and outdoor ambient temp. of 35°C DB.
Heating : heat water inlet/outlet: 40˚C / 45˚C, and outdoor ambient temp. 7˚C DB/6°C WB.
Water side fouling factor: 0.086m
2