Part 5 – Diagnosis and Troubleshooting 
5.6 E0, E8 Troubleshooting 
 Digital display output 
     
 
 Procedure 
 
E0: Water flow malfunction(after 3 
times E8) 
E8: Water flow malfunction 
Water flow switch connection on main 
PCB is loose
1
 
Ensure the switch is connected properly 
Water flow is insufficient 
Check the water piping and valves. Make 
sure the water piping is clean, there is no 
air in the water piping and all valves are 
open.   
Water flow switch is damaged 
Replace the water flow switch 
Replace hydronic system PCB 
 
Note:   
2.  Water flow switch connection is port CN16 on the refrigerant system PCB