5.21 P1 Troubleshooting 
 Digital display output 
 
 
 Procedure 
 
P1: High pressure switch protection 
High pressure switch connection is loose
1
 
Ensure the pressure switch is connected 
properly 
Too much refrigerant is charged in the 
system 
Release the right amount of refrigerant 
The water flow rate is not sufficient in 
heating mode 
Check water side heat exchanger, water 
piping, circulator pumps and water flow 
switch for dirt/blockages in order to 
increase the water flow rate 
The air side heat exchanger heat 
exchange is poor in heating mode 
Check air side heat exchanger, fan(s) and 
air outlets for dirt/blockages. 
Moisture in the system; The high 
pressure side is blocked
2
: Filter or EXV is 
blocked by ice; crushed or bent 
pipe ;Impurities in the pipes 
The piping should be cleaned and the 
refrigerant system should be vacuumed 
Outlet water temperature sensor (TW-
out) connection on main PCB is loose
3
 
Ensure the temperature sensors are 
connected properly 
Pressure switch has short-circuited or 
failed
4
 
Replace the pressure switch