Midea ESG-Inv M Series Pool Heat Pump Manual 
5.25 Pb Troubleshooting 
 Digital display output 
 
 
 Protection logic 
Pb: Anti-freeze mode 
 
Anti-freeze is used to protect the water system from cracking during winter. It is normal protection operation and heat pump 
will return to the normal operation automatically. 
 
Heating mode 
 
Cooling mode 
 
   
Ambient  temperature  <  3°C, 
inlet water temperature < 5°C 
Or 
Ambient  temperature  <  3°C, 
leaving water temperature < 5°C 
Or 
Leaving water temperature < 2°C 
Ambient temperature > 3°C, 
inlet water temperature > 5°C 
Or 
Ambient  temperature  >  3°C, 
leaving water temperature > 5°C 
Or 
Leaving water temperature > 2°C 
Inlet  water  temperature  <  4°C 
  Or 
Leaving water temperature < 4°C 
Inlet water temperature > 4°C 
Or 
Leaving water temperature > 4°C