Midea ESG-Inv M Series Pool Heat Pump Manual 
5.8 E2 Troubleshooting 
 Digital display output 
 
 
 Procedure 
 
E2: Communication malfunction 
between controller and main control 
board 
Interference from high voltage (220V or 
higher) wires 
Ensure the communication wires and 
high voltage wires are separated 
Communication wires are close to a 
source of electromagnetic radiation such 
as transformer or strong fluorescent lamp 
Remove the source of interference, or 
add additional shielding to the 
communication wires 
Communication wires have short 
circuited, disconnected or are 
misconnected 
Reconnect the communication wires 
Communication wires are not connected 
in a daisy chain 
Connect the communication wires in a 
daisy chain 
Replace main PCB or controller