5.15 H6, HH Troubleshooting 
 Digital display output 
     
 
 Procedure 
 
H6: The DC fan malfunction 
HH: 10 times H6 in 2 hours 
Strong wind is blowing towards the 
fan, making the fan running in the wrong 
direction or the fan speed is too high or 
too slow   
Changer the outdoor unit’s installation 
direction or build a shelter to protect the 
fan from strong wind 
Power wires or communication wires of 
fan are not connected properly 
Ensure power and communication wires 
are connected properly 
The power supply is abnormal 
Check the power supply equipment 
The fan motor is blocked or has failed 
Remove obstruction or replace the fan 
motor 
Replace inverter module PCB 
 
 Protection logic 
 
 
When H6 protection occurs 10 times in 120 minutes, the HH error is displayed. When an HH error occurs, a manual system 
restart is required before the system can resume operation. 
 
 
After fan starts, fan speed < 50rpm for more than 40s 
Or 
Fan  speed  <  50rpm  for  3s 
After 30s, the unit restarts automatically