Midea ESG-Inv M Series Pool Heat Pump Manual
5.24 P5 Troubleshooting
Digital display output
Procedure
P5: |TW-out-TW-in| value too big
protection
Inlet water temperature sensor (TW-in),
outlet water temperature sensor is not
installed
Installed the temperature sensor
Inlet water temperature sensor (TW-in),
outlet water temperature sensor
1
connection on main PCB is loose
Ensure the sensor is connected properly
Inlet water temperature sensor (TW-in),
outlet water temperature sensor is
affected by moisture or water
Inlet water temperature sensor (TW-in),
outlet water temperature sensor has
short-circuited or failed
The water flow rate is not sufficient,
caused by pump not working, crushed or
bent water piping, high resistance in
water piping
Ensure water pump works, maximum
system head is within pump head and
flow rate range
Valves in the water system are closed.
Poor water quality or water piping
contains air
Clean the water system and purge air
from the water system