EasyManua.ls Logo

Midea ESG-Inv M Series - Page 44

Midea ESG-Inv M Series
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ESG-Inv M
43
Part 5 – Diagnosis and Troubleshooting
5.12 F6 Troubleshooting
Digital display output
Procedure
H6: EXV1 fault
The EEV1 connector of the main PCB is loose or not
inserted
Yes
Ensure the connection is well
No
The coil of electronic expansion valve is damaged
Yes
Replace the coil of electronic expansion
valve
No
Replace main PCB
Note:
1. EXV connection is port CN33 on the main PCB
MBT Confidential

Related product manuals