Part 5 – Diagnosis and Troubleshooting
Situation 2: L1 or L2 error appears after the compressor has been running for a period of time and the compressor speed
is over 20rps
Re-start the unit once the power supply
has returned to normal
DIP Switch S1 setting is wrong
Refer to the wiring diagram to reset the
S1 setting
Replace the inverter module
1
Notes:
1. When replacing an inverter module, a layer of thermally conductive silica gel should be painted on IPM module (on the reverse side of the inverter module
PCB).
L5/L7 troubleshooting
The wire is not connected properly
Ensure wire is connected properly
Inverter module PCB has malfunctioned
Replace inverter module PCB
1
Note:
1. When replacing an inverter module, a layer of thermally conductive silica gel should be painted on IPM module (on the reverse side of the inverter module
PCB).
L3 troubleshooting
Replace the inverter module PCB