Flooded type water cooled screw chiller (PCB Control) MCAC-CTSM-2012-11
35
Note:
“Max” in the upper left indicates the upper limit of the setting parameter; “Min” in the upper right
indicates the lower limit.
“Automatic On/Off”: Only displaying under Timed mode.
Explanation:
Setting Temp. (Chilled Leaving Water): The target temperature of the chiller leaving water
Temp. / Compressor start (Chilled Leaving Water): One of the compressor starting conditions
required to be achieved for the chilled leaving water temperature. The compressor can start only at
the current chilled leaving water temperature the setting value in cooling mode, or the current
chilled leaving water temperature the setting value in heating mode.
Temp. Adjustment Period: The time interval between two temperature detections.
Temperature Control Range: Indicating the precision of the temperature control. For example, the
factory default setting is 2 ℃,it means when the temperature is in the range of the setting
temperature ± 0.5℃,the unit will not execute the loading or unloading action.
Clock Setting
Clock Setting
Click on the numerical box, the numeric keyboard will appear, input the time, click “ENT” to save and
take effect. Click “ESC” to cancel the input value.
Note: Please pay special attention in setting of time and date to the fact that setting of
Manual
input is
allowed