Aqua Tempo Super II
22 201709
Midea Aqua Tempo Super II
Service Manual
superheat and compressor frequency, and uses the suction temperature, air side heater exchanger temperature,
discharge temperature to modify the control.
When the outdoor unit is in standby:
The EXV is at position 352 (steps).
When the outdoor unit stops:
The EXV first closes fully, then moves to the standby position (352 (steps)).
5.7 Outdoor Fan Control
The speed of the outdoor unit fan(s) is adjusted in steps, as shown in Table 3-5.3.
Table 3-5.3: Outdoor fan speed steps
Fan speed index
Fan speed (rpm)
30kW
60kW
FAN A
FAN A
FAN B
0
0
0
0
1
150
150
0
2
200
200
0
3
250
250
0
4
300
300
250
5
360
360
300
6
430
430
360
7
480
530
460
8 (super silent mode)
530
650
580
9
650
760
680
10(silent mode)
710
850
800
11
800
900
850
12(standard ESP mode)
820
950
900
Abbreviations:
ESP: External static pressure

Table of Contents

Other manuals for Midea MC-SU60-RN1L

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MC-SU60-RN1L and is the answer not in the manual?

Midea MC-SU60-RN1L Specifications

General IconGeneral
BrandMidea
ModelMC-SU60-RN1L
CategoryChiller
LanguageEnglish

Related product manuals