EasyManuals Logo

Midea MC-SU60-RN1L Service Manual

Midea MC-SU60-RN1L
101 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #80 background imageLoading...
Page #80 background image
Aqua Tempo Super II
201709 79
Part
4 - Diagnosis and Troubleshooting
4.14 P9 Troubleshooting
Digital display output 4.14.1
Description 4.14.2
High temperature difference between water side heat exchanger water inlet and water outlet temperatures
protection.
All units stop running.
Error code is displayed on main PCB and user interface.
Possible causes 4.14.3
Temperature sensor not connected properly or has malfunctioned.
Water piping contains air.
Insufficient water flow.
Main PCB damaged.

Table of Contents

Other manuals for Midea MC-SU60-RN1L

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MC-SU60-RN1L and is the answer not in the manual?

Midea MC-SU60-RN1L Specifications

General IconGeneral
BrandMidea
ModelMC-SU60-RN1L
CategoryChiller
LanguageEnglish

Related product manuals