The available external static pressure function for water flow is 
shown in the graph below.
10.6 Setting the pump speed
The default setting is the highest speed (III). 
If the water flow in the system is too high 
the speed can be 
set to low (I).
The pump speed can be selected by 
adjusting the red knob on the pump. The 
notch point indicates pump speed.
5.  Ground wiring
     Make sure that the ground wires have been connected properly 
     and that the ground terminals are tightened.
6.  Internal wiring
     Visually check the switch box for loose connections or damaged 
     electrical components.
7.  Mounting
     Check that the unit is properly mounted, to avoid abnormal noises 
     and vibrations when starting up the unit.
8.  Damaged equipment
     Check the inside of the unit for damaged components or 
     squeezed pipes.
9.  Refrigerant leak
     Check the inside of the unit for refrigerant leakage. If there is a 
     refrigerant leak, call your local dealer.
10.Power supply voltage
     Check the power supply voltage on the local supply panel. The
     voltage must correspond to the voltage on the identification label
     of the unit.
11.Air purge valve
     Make sure the air purge valve is open (at least 2 turns).
2.  Fuses, circuit breakers, or protection devices
     Check that the fuses or the locally installed protection devices are 
     of the size and type specified in the chapter 14 Technical 
 specifications. Make sure that no fuses or protection devices 
     have been bypassed.
3.  Backup heater circuit breaker
     Do not forget to turn on the backup heater circuit breaker in the 
     switchbox (it depends on the backup heater type). Refer to the 
     wiring diagram.
4.  Booster heater circuit breaker 
     Do not forget to turn on the booster heater circuit breaker  (applies
     only to units with optional domestic hot water tank installed).
10.5 Powering up the unit
Operating the system with closed valves will damage the 
circulation pump!
12.Shut-off valves
     Make sure that the shut-off valves are fully open
When power to the unit is turned on, "1%~99%" is displayed on the 
user interface during  initialization. During this process the user 
interface cannot be operated.
0
10
20
30
40
50
60
70
80
90
0.3 0.8 1.3 1.8 2.3 2.8 3.3
Flowrate(m³/h)
available external stac pressure VS flowrate 
(1-phase 10-16kW + 3-phase 12~16kW)
Ⅲ
Ⅱ
Ⅰ
0
10
20
30
40
50
60
70
0.3 0.5 0.7 0.9 1.1 1.3 1.5 1.7 1.9 2.1 2.3
Flowrate(m³/h)
available external stac pressure VS flowrate
(5/7/9kW)
Ⅲ
Ⅱ
Ⅰ
 Checks before initial start-up
10.4 Pre-operation checks
10.3 Initial start-up at low outdoor ambient temperatures
During initial start-up and when water temperature is low, it is 
important that the water is heated gradually. Failure to do so may 
result in concrete floors cracking due to rapid temperature change.
Please contact the responsible cast concrete building contractor for 
further details.
To do so, the lowest water flow set temperature can be decreased to 
a value between 25°C and 35°C by adjusting the FOR SERVICEMAN. 
Refer to "FOR SERVICEMAN/special function/preheating for floor" .
Switch off the power supply before making any connections.
DANGER
After the installation of the unit, check the following before switching 
on the circuit breaker:
1.  Field wiring
     Make sure that the field wiring between the local supply panel and 
     unit and valves (when applicable), unit and room thermostat (when 
     applicable), unit and domestic hot water tank, and unit and backup 
     heater box have been connected according to the instructions 
     described in the chapter 9.6 Field wiring, according to the wiring 
     diagrams and to local laws and regulations.
38
38