11 TEST RUN AND FINAL CHECK
The installer is obliged to verify correct operation of unit after 
installation.
 12 MAINTENANCE AND SERVICE
In order to ensure optimal availability of the unit, a number of checks 
and inspections on the unit and the field wiring have to be carried 
out at regular intervals.
This maintenance needs to be carried out by your local technician. 
In order to ensure optimal availability of the unit, a number of checks 
and inspections on the unit and the field wiring have to be carried out 
at regular intervals.
This maintenance has to be carried out by your local Midea technician.
11.1 Final check
Before switching on the unit, read following recommendations:
■  When the complete installation and all necessary settings have 
    been carried out, close all front panels of the unit and refit the unit 
    cover.
■  The service panel of the switch box may only be opened by a 
    licensed electrician for maintenance purposes.
11.2 Test run operation (manual)
If required, the installer can perform a manual test run operation at 
any time to check correct operation of air purge, heating, cooling 
and domestic water heating, refer to 10.7 Field settings/test run.
ELECTRIC SHOCK
■  Before carrying out any maintenance or repair activity, 
    always switch off the circuit breaker on the supply panel, 
    remove the fuses (or switch off the circuit breakers) or 
    open protection devices of the unit.
■  Make sure that before starting any maintenance or repair 
 activity that the power supply to the outdoor unit is switched off.
■  Do not touch live parts for 10 minutes after the power 
    supply is turned off because of high voltage risk.
■  The heater for the compressor may operate even in stop mode.
■  Please note that some sections of the electric component 
    box are hot.
■  Make sure you do not touch a conductive section.
■  Do not rinse the unit. This may cause electric shocks or 
    fire.
■  When service panels are removed, live parts can be easily 
    touched by accident.
    Never leave the unit unattended during installation or 
    servicing when service panel is removed.
The described checks must be executed at least once a year by 
qualified personnel.
1.  Water pressure
     Check if the water pressure is above 1 bar. If necessary add 
     water.
2.  Water filter
     Clean the water filter.
3.  Water pressure relief valve 
     Check for correct operation of the pressure relief valve by turning 
     the black knob on the valve counter-clockWise:
     ■  If you do not hear a clacking sound, contact your local dealer.
     ■  In case the water keeps running out of the unit, close both the 
         water inlet and outlet shut-off valves first and then contact your 
         local dealer.
4.  Pressure relief valve hose
     Check that the pressure relief valve hose is positioned 
     appropriately to drain the water.
5.  Backup heater vessel insulation cover
     Check that the backup heater insulation cover is fastened tightly 
     around the backup heater vessel.
6.  Domestic hot water tank pressure relief valve (field supply) 
     Applies only to installations with a domestic hot water tank.
     Check for correct operation of the pressure relief valve on the
     domestic hot water tank.
7.  Domestic hot water tank booster heater
     Applies only to installations with a domestic hot water tank.
     It is advisable to remove lime buildup on the booster heater to 
     extend its life span, especially in regions with hard water. To do 
     so, drain the domestic hot water tank, remove the booster heater 
     from the domestic hot water tank and immerse in a bucket (or 
     similar) with lime-removing product for 24 hours.
8.  Unit switch box
     ■  Carry out a thorough visual inspection of the switch box and 
         look for obvious defects such as loose connections or defective
         wiring.
     ■  Check for correct operation of contactors with an ohm meter. 
         All contacts of these contactors must be in open position.
9.  Use of glycol
     (Refer to 9.3 Water pipework Caution: "Use of glycol" )
     Document the glycol concentration and the pH-value in the 
     system at least once a year.
     ■  A PH-value below 8.0 indicates that a significant portion of the 
         inhibitor has been depleted and that more inhibitor needs to be
         added.
     ■  When the PH-value is below 7.0 then oxidation of the glycol 
         occurred, the system should be drained and flushed thoroughly
         before severe damage occurs.
     Make sure that the disposal of the glycol solution is done in
     accordance with relevant local laws and regulations.
DANGER
NOTE
That during the first running period of the unit, required power 
input may be higher than stated on the nameplate of the unit. This 
phenomenon originates from the compressor that needs elapse of 
a 50 hours run in period before reaching smooth operation and 
stable power consumption.
13 TROUBLE SHOOTING
This section provides useful information for diagnosing and 
correcting certain troubles which may occur in the unit.
This troubleshooting and related corrective actions may only be 
carried out by your local technician.
13.1 General guidelines
Before starting the troubleshooting procedure, carry out a thorough 
visual inspection of the unit and look for obvious defects such as 
loose connections or defective wiring.
49