22
Frequency of Refrigerant Leak Checks:
1)Forequipmentthatcontainsuorinatedgreenhousegasesinquantitiesof5tonnesofCO2equivalentormore,but
of less than 50 tonnes of CO2 equipment,at least every 12 months, or where a leakage detection system is installed,
at least every 24 months.
2)Forequipmentthatcontainsuorinatedgreenhousegasesinquantitiesof50tonnesofCO2equivalentormore,but
oflessthan500tonnesofCO2equipment,atleasteverysixmonths,orwherealeakagedetectionsystemisinstalled,
at least every 12 months.
3)Forequipmentthatcontainsuorinatedgreenhousegasesinquantitiesof500tonnesofCO2equivalentormore,at
leasteverythreemonths,orwherealeakagedetectionsystemisinstalled,atleasteverysixmonths.
4)Non-hermeticallysealedequipmentchargedwithuorinatedgreenhousegasesshallonlybesoldtotheenduser
whereevidenceisprovidethattheinstallationistobecarriedoutbyanundertakingcertiedperson.
5)Onlycerticatedpersonisallowedtodoinstallation,operationandmaintenance.
NOTE
8.5 Water quality limitations
If the water quality does not meet the requirements in the table below, please contact the supplier for advice.
NOTE
Table 8-2
PH Value Total Hardness
Electrical
Conductivity
6.5-8.0 50ppm <200μS/cm(25°C)
Sulphate Ion Silicon Iron Content
<50ppm <30ppm <0.3ppm
SuldeIon Chloride Ion Ammonia Ion
None <50ppm None
Sodium Ion Calcium Ion
None <50ppm