Programming and Calibration
The following parameters are in the Automatic Parameter Access (APA) loop. Press
"ENTER"
once to accept
the current parameter value and proceed to the next parameter. To alter a parameter value, key in the new
value and press
"ENTER"
. Press
"ENTER"
again to advance to the next parameter.
with
[P ]
displayed
press
"ENTER"
[P01 1]
displayed, Belt Scale Application
press
"ENTER"
[P02 1]
displayed, Load Cell Input
press
"ENTER"
[P0 1] displayed, Rate Units = MTPH
key in value, 1 = MTPH
2 = KG/H
3 = LTPH
4 = STPH
5 = LB/H
press
"ENTER"
[P1 0.000]
displayed, Design Rate = 0
key in value, (Rate from Design Data Sheet)
press
"ENTER"
[P2 1.000]
displayed, Local Totalizer Update = every 1 unit.
key in value, (refer to Parameters, P2)
press
"ENTER"
[P3 1.000]
displayed, Remote Totalizer Update = every 1 unit.
key in value, (refer to Parameter Listing, P3)
press
"ENTER"
[P4 0.000] displayed, Belt Speed = 0
key in value, (Belt Speed from Design Data Sheet)
press
"ENTER"
[P5 ####] displayed, Speed Constant (refer to Parameter Listing)
key in value, (Speed Constant, only if a speed sensor is utilized)
PL-516 31