P2 Local Totalizer
Defines the amount of material to be registered by the Compu-M prior to initiating an internal totalizer update.
The weight unit portion of the Rate Unit (P0) selected is assumed. (F = 1)
P2 Value Total Display # of Weight Units
enter: .001 = ####.### = thousandths
.01 = #####.## = hundredths
.1 = ######.# = tenths
1 = ######## = units (F = 1.000)
10 = #######0 = tens
100 = ######00 = hundreds
1000 = #####000 = thousands
If the value selected is too low, the Compu-M will display
[E2]
.
Enter a higher value.
P3 Remote Total
Defines the amount of material to be registered by the Compu-M prior to initiating a relay contact closure which
may be utilized for remote totalization. The weight unit portion of the Rate Unit (P0) selected is assumed.
weight units contact closures
enter: .001 = 1
.01 = 1
.1 = 1
1 = 1
10 = 1
100 = 1
1000 = 1
If the value selected is too low, the Compu-M will display
[E2]
.
Enter a higher value.
P4 Belt Speed (Belt Scale Applications Only)
Defines the Design Speed of the conveyor belt. After initial calibration, belt speed adjustments may be entered
via P17 to avoid performing a new initial zero and span calibration.
The speed units are assumed to be:
metres/sec, if P0 = 1 (MTPH)
2 (KG/H)
feet/min, if P0 = 3 (LTPH)
4 (STPH)
5 (LB/H)
enter: Design Belt Speed from Design Data Sheet. (F = 0.000)
PL-516 60