P16 Remote Totalizer Relay Closure
Defines the on-time duration of the remote totalizer relay contact closure. The on/off cycle time for this relay is
automatically determined by the operator entered values of Rate (P1) and Remote Total (P3). To determine
the on-time duration required, refer to the specifications stated by the manufacturer of the remote totalizer (or
other device) to be utilized. If the combination of the values entered in P1, P3, and P16 exceed the operating
limits of the system the Compu-M will display,
[E2]
, indicating the value of P3 should
be increased.
1 = 32 msec 6 = 192 msec
2 = 64 msec 7 = 224 msec
3 = 96 msec 8 = 256 msec
4 = 128 msec 9 = 288 msec
5 = 160 msec
enter: desired value
P17 Speed Constant Adjust (Belt Scale Applications Only)
Prior to the initial entry of a value into this parameter, the current dynamic belt speed is displayed. If the speed
displayed by the Compu-M is not equal to the actual belt speed, enter the actual belt speed. The use of this
parameter does not require a system recalibration.
Where a Speed Sensor is not used, (TB1-13,14 jumpered), the entry of the new or measured belt speed value
causes the Compu-M to automatically alter the Belt Speed (P4) value.
Where a Speed Sensor is used, (TB1-14 open), the entry of the new or measured belt speed value causes
the Compu-M to automatically alter the Speed Constant (P5) value.
enter: new or measured speed
P18 Rate Output Damping
Defines the level of damping to be applied to the Analog mA output. The use of this parameter permits
variations in stabilization between the Compu-M local displays, and the Rate Output. Analog mA Output
damping equals Display damping if P18 = 0. The range of possible values is 0 - 9999, dependent upon the
value entered in P11.
enter: Rate Output Damping, desired (F = 0)
PL-516 65