P95 Load Cell Balance (Belt Scale Applications Only)
Utilizes the display values entered sequentially from P91 through P94 to calculate and display a value
representative of the load cell input signal balance. Without disturbing the test weight position (P93), the
operator adjusts the Compu-M board B "A BAL" potentiometer while observing the effect on the displayed
value. The load cell signal inputs are sufficiently balanced when the value displayed equals 0
+ 5 counts.
Pressing "
ENTER
" returns the display to P91, to exit the loop press any other command key.
Should the "A BAL" potentiometer of a calibrated Compu-M
require adjustment, an initial zero and span calibration must be
performed. A material test may be required to verify system accuracy.
P99 Reset
Initiates a Compu-M memory reset. This feature clears undesired data from the Compu-M memory and
restores parameter values to the original factory settings. The implementation of a Reset requires total
reprogramming and calibration.
select P99
press
"ENTER"
[P99 0]
displayed
press
"9"
,
[P99 9]
displayed
press
"ENTER"
(diagnostic messages temporarily displayed)
[P ]
displayed, Reset complete.
PL-516 71