P88 Initial Span
Activates a Span calibration which the Compu-M will utilize as a reference to which subsequent routine span
calibrations will be compared.
This parameter is generally utilized in response to a Display Message
[E4]
, when an accountable but
mechanically non-recoverable zero calibration deviation, greater than 12.5% of span has occurred.
Refer to the appropriate recalibration section of this manual.
enter:
"1"
, Initial Span (F = 0)
P91 Calculator Input 1 (Belt Scale Applications Only)
Displays the count reference value of the summed inputs from load cell A and B when Compu-M board B
switch SW1 is closed. Placing the test weight on load cell B side of the belt scale and entering the displayed
value automatically advances the display to the next sequential parameter.
P92 Calculator Input 2 (Belt Scale Applications Only)
Displays the count reference value of the load cell B input when Compu-M board B switch SW1 is open.
Without disturbing the test weight position (P-91), entering the value displayed automatically advances the
display to the next sequential parameter.
P93 Calculator Input 3 (Belt Scale Applications Only)
Displays the count reference value of the load cell B input when Compu-M board B switch SW1 is open.
Placing the test weight on the load cell A side of the belt scale and entering the value displayed automatically
advances the display to the next sequential parameter.
P94 Calculator Input 4 (Belt Scale Applications Only)
Displays the count reference value of the summed inputs from load cell A and B when Compu-M board B
switch SW1 is closed. Without disturbing the test weight position (P93), entering the value displayed
automatically advances the display to the next sequential parameter.
PL-516 70