P-55 high total
the parameter will display the 4 highest digits of the 8 digit totalizer
used in pump totalizer or OCM applications. The parameter will
also allow the display to be reset to any value. ( F = 0000 )
P-56 remote totalizer contact control.
a momentary closure of the remote totalizer contact occurs
once each time the entered flow or pumped volume has passed.
enter option: – 3 = 0.001
– 2 = 0.01
– 1 = 0.1
0 = 1( F )
1 = 10
2 = 100
3 = 1,000
4 = 10,000
5 = 100,000
6 = 1,000,000
7 = 10,000,000
P-57 flow sampler control
&
P-58
a momentary closure of the flow sampler contact occurs once each
time a volume of y x 10
x
, as defined by P-57 (x) and P-58 (y),
flows or is pumped.
enter P-57 (x) = base 10 exponent, – 3 to 7 ( F = 0 )
enter P-58 (y) = mantissa, 0.001 to 9999 ( F = 1.000 )
e.g. if P-57 = 3 and P-58 = 5, then a sampler contact closure will
occur each time 5 x 10
3
= 5000 units of volume has passed
P-59 time sampler control
a momentary closure of the time sampler contact occurs each
time the entered amount of time in hours has elapsed ( F = - - - - )
PL-443 7 – 14