6 - 20
REPLACEMENT OF CC-LINK
6
(b) Link special register (SW)
: Compatible, : Partial change required, × : Incompatible
Number
Name Compat-
ibility
Precautions for replacement
AJ61BT11/A1SJ61BT11 QJ61BT11N
SW000B
-
Dedicated instruction retry
count setting Added on the Q series and
replacement is not applied.
SW0014 to SW0017
Specification of remote device
station to be initialized.
SW0043
Master station switch data link
start result
Refresh instruction at standby
master switching result
The specifications of A/AnS
series and Q series are the
same.
SW0052
-
Automatic CC-Link startup
execution result
Added on the Q series and
replacement is not applied.
SW0058 Detailed LED display status
SW0059 Transmission rate setting
SW005D
Forced master switching
instruction result
SW005F
Remote device station
initialization procedure
registration instruction result
SW0062 Condition setting switch status Module operating status
On the Q series, parameter
setting status is stored.
SW00B9
E
2
PROM registration status
-
No E
2
PROM (Refer to Section
6.7.)
SW00BA
E
2
PROM erasure result
SW00BB
Number of times when
parameters can be registered
to E
2
PROM
SW0110 to SW011F
-
Remote device station
initialization procedure
registration execution
individual information (target 1
to 16)
Added on the Q series and
replacement is not applied.
SW0140 to SW0143
Compatible CC-Link Ver.
information
SW0144 to SW0147
CC-Link Ver.
installation/parameter
matching status
SW0148 Parameter mode
SW0149 Host parameter mode
SW0183 Transmission speed test result
SW0184 to SW0187
Transmission speed test result
for each station