2 Specification
2.5 Output Specifications
18
FX3U-1PG User's Manual
2.5 Output Specifications
2.5.1 Output specifications
2.5.2 Internal output circuit
For the internal output circuit diagram, refer to the following.
Refer to Section 5.2.
Item Specification
Output signal name
Group 1
FP: Forward pulse or pulse train
RP: Reverse pulse or direction signal
Group 2 CLR: CLR signal
Group 1
Output form Transistor
Output system
Forward (FP) and reverse (RP) pulse or pulse (PLS) with direction (DIR) can be
selected.
Output frequency 1 Hz to 200 kHz
Rated load voltage 5 to 24 V DC
Max. load current 20 mA or less
VIN current consumption 5 to 24 V DC 35 mA or less
Output ON voltage 1.0 V or less
Operation display LED ON at output ON
Group 2
Output form Transistor
Output system Pulse (Output pulse width: 20 ms)
Rated load voltage 5 to 24 V DC
Max. load current 20 mA or less
Output ON voltage 1.5 V or less
Operation display LED ON at output ON