146
APPX
Appendix 3 Buffer Memory
EtherNet/IP data link continuation specification
EtherNet/IP data link continuation specification request (Un\G16634)
This address is used to set whether to continue EtherNet/IP communications when 'EtherNet/IP communication start request'
(Y10) is turned on and off.
Set this address to continue EtherNet/IP communications in situations such as when the CPU module changes from the RUN
state to the STOP state and when a stop error occurs on the CPU module.
The setting is reflected when 'EtherNet/IP communication start request' (Y10) is turned off and on.
0: Stops EtherNet/IP communications.
16: Continues EtherNet/IP communications.
EtherNet/IP data link continuation specification state (Un\G16635)
This address is used to store the setting status of 'EtherNet/IP data link continuation specification request' (Un\G16634).
The setting is reflected when 'EtherNet/IP communication start request' (Y10) is turned off and on.
0: The 'EtherNet/IP data link continuation specification request' (Un\G16634) setting has not been reflected.
1: Operation is in progress with the setting for continuing EtherNet/IP communications.
2: Operation is in progress with the setting for stopping EtherNet/IP communications.
Class1 I/O data size
Class1 Input data length (Un\G16640 to Un\G16895)
This address is used to store the size of the data received by the RJ71EIP91 from the EtherNet/IP device during Class1
communications. (Unit: words)
Class1 Output data length (Un\G16896 to Un\G17151)
This address is used to store the size of the data to send to the EtherNet/IP device from the RJ71EIP91 during Class1
communications. (Unit: words)
Setting status
MAC Address (Un\G25733 to Un\G25735)
Stores the MAC address of the RJ71EIP91.
The MAC address is stored starting with the lower-order word.
Ex.
For MAC address 08-00-70-00-1A-34
Address Description
Un\G16640 Stores the input data size of connection number 1.
Un\G16641 Stores the input data size of connection number 2.
Un\G16895 Stores the input data size of connection number 256.
Address Description
Un\G16896 Stores the output data size of connection number 1.
Un\G16897 Stores the output data size of connection number 2.
Un\G17151 Stores the output data size of connection number 256.
Address Stored value Description
Un\G25733 1A34H First lower-order word of MAC address
Un\G25734 7000H Second lower-order word of MAC address
Un\G25735 0800H Third lower-order word of MAC address

Table of Contents