1 FUNCTIONS
1.7 Redundant System Function
103
1
6. Set the redundant function module of the own system as the system A in the "System A/B Setting" window, and reset the
CPU modules of both systems or power off and on the both systems.
[Online] [Redundant PLC Operation] [System A/B Setting]
7. Write the set parameters to the system A CPU module.
[Online] [Write to PLC]
8. Click the [Yes] button to write to the CPU modules of both systems.
9. Either reset the CPU modules of both systems or power off and on both systems.
In this setting example, default settings are used for the parameters other than those described. For the
parameter setting, refer to the chapter explaining the parameters in this manual. ( Page 124
PARAMETER SETTINGS)