3 PROGRAMMING
3.4 Communication Example of Safety Communication Function Used in Redundant Master Stations
189
3
Intelligent device station setting
Connect the engineering tool to the remote head module, and set parameters.
1. In the following window, set the remote head module.
2. In the following window, set the items for Base/Power/Extension Cable Setting.
[Navigation window] [Parameter] [System Parameter] [I/O Assignment] tab [Base/Power/Extension Cable
Setting]
3. In the I/O assignment setting, set the I/O module with diagnostic functions to be mounted.
[Navigation window] [Parameter] [System Parameter] [I/O Assignment] tab [I/O Assignment Setting]
4. Set the items in "Network Required Setting" of "CPU Parameter" as follows.
[Navigation window] [Parameter] [RJ72GF15-T2] [CPU Parameter] [Network Required Setting]