3 PROGRAMMING
3.4 Communication Example of Safety Communication Function Used in Redundant Master Stations
191
3
Master station setting
Connect the engineering tool to the SIL2 Process CPU of the master station, and set parameters.
In a system using the SIL2 Process CPU, the same program and parameter are written to both systems. A new project does
not need to be created for the standby system.
1. In the following window, set the SIL2 Process CPU.
[Project] [New]
2. In the following window, enter a password and re-enter password, and click the [OK] button.