1 FUNCTIONS
1.7 Redundant System Function
107
1
Settings of slave station
Connect the engineering tool to the remote head module of the remote head No.1 and set parameters.
In a redundant system, the same parameters are written to both systems. A new project does not need to be created for the
standby system.
1. In the following window, set the remote head module.
[Project] [New]
2. In the I/O assignment setting, set the remote head No.2 for slot No.0.
[Navigation window] [Parameter] [System Parameter] [I/O Assignment] tab [I/O Assignment Setting]
3. Set the content of "Network Required Setting" of "CPU Parameter" as follows.
[Navigation window] [Parameter] [RJ72GF15-T2(LR)] [CPU parameter] [Network Required Setting]
4. Set the module parameters for the module mounted on the remote head module. ( Manual for the module used)
5. Write the set parameters to the remote head No.1, then reset or power on and off the remote head No.1 and 2.
[Online] [Write to PLC]
In this setting example, default settings are used for the parameters other than those described. For the
parameters, refer to the following.
MELSEC iQ-R CC-Link IE Field Network Remote Head Module User's Manual (Application)