1 FUNCTIONS
1.1 Cyclic Transmission
When there is a remote device station in the network, use station-based block data assurance. If it is disabled,
the functions of the remote device station cannot be assured.
32-bit data assurance
The RWr and RWw data can be assured in 32-bit units.
Data assurance at the time of direct access to link devices
When link refresh target devices are accessed, the integrity of 32-bit data can be assured by satisfying the following
conditions.
The start device number of RWr, RWw is multiples of 2.
The number of points assigned to RWr, RWw is multiples of 2.
Data integrity assurance at the time of access to buffer memory
The integrity of 32-bit data can be assured by satisfying the following conditions.
Access using the DMOV instruction
The start address of the buffer memory is multiples of 2.
For data assurance of more than 32 bits, use station-based block data assurance or interlock programs.
0H
1H
2H
3H
4H
5H
6H
7H
RWr, RWw
2 words
(32 bits)
Master/local module
Device
CPU module
Link refresh
2 words
(32 bits)
2 words
(32 bits)
2 words
(32 bits)
2 words
(32 bits)
2 words
(32 bits)
2 words
(32 bits)
2 words
(32 bits)
0H
1H
2H
3H
4H
5H
6H
7H
2 words
(32 bits)
Buffer memory
Master/local module
2 words
(32 bits)
2 words
(32 bits)
2 words
(32 bits)
DMOV instruction
\