4 TROUBLESHOOTING
4.5 List of Error Codes
D257H The request type of the REQ instruction is incorrect. • Execute again after correcting the request type in
the request data.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D258H The control station does not exist when the dedicated
instruction was executed to the specified control
station or current control station.
• Execute again after correcting the target station
number in the control data.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D25AH The dedicated instruction was executed specifying the
channel in use.
• Retry the operation after a while.
• Change the channels used by own station or the
target station's channel in the control data.
D25BH The dedicated instruction was executed specifying the
channel in use.
Change the channels used by own station or the
target station's channel in the control data.
D25CH The function version specification of the dedicated
instruction is incorrect.
• The value set for the control block of the dedicated
instruction is out of range. Execute again after
correcting the value.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D25DH The transient data is incorrect. • Correct the transient data at the request source,
and retry the operation.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D25EH Dedicated instructions which cannot be executed
simultaneously were executed.
• Another CC-Link dedicated instruction is in
execution. Execute again after a while.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D25FH The REMFR/REMTO/REMFRD/REMTOD instruction
was executed from a module with a station type which
cannot execute it.
The REMFR/REMTO/REMFRD/REMTOD instruction
can only be used for the master station, local station,
and submaster station. Modify the program to the one
without the REMFR/REMTO/REMFRD/REMTOD
instructions.
D260H The REMTO/REMTOD instruction was executed from
the module with a station type which cannot execute it.
The REMTO/REMTOD instruction can only be used
for a master operating station.
D261H The CCPASET instruction was executed from the
module with a station type which cannot execute it.
Parameter setting using the CCPASET instruction
cannot be configured on local stations. Configure the
parameter setting on the master station.
D262H The total number of slave stations specified in the
CCPASET instruction is incorrect.
• Execute again after correcting the total number of
slave stations in the control data.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D263H The constant link scan time setting of the CCPASET
instruction is incorrect.
• Execute again after correcting the constant link
scan time in the control data.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D264H The station number setting of the CCPASET
instruction is incorrect.
• Execute again after correcting the station number in
the setting data within 1 to 120.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D265H The station number specified for the CCPASET
instruction is already in use.
• Execute again after correcting the station number in
the setting data to a unique value.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D266H The slave station setting information of the CCPASET
instruction is incorrect.
• Execute again after correcting the slave station
setting information in the setting data.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D267H The station type of the CCPASET instruction is
incorrect.
• Execute again after correcting the station type in the
sett
i
ng data.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D268H The link device range assignment specified for each
station in the CCPASET instruction is incorrect.
• Execute again after correcting the offset or size of
the slave station link device in the setting data.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.