11. OPTIONS AND AUXILIARY EQUIPMENT
11 - 28
(b) Example of selecting the wire sizes
When connecting multiple servo amplifiers, always use junction terminals for wiring the servo
amplifier terminals P, N-. Also, connect the servo amplifiers in the order of larger to smaller
capacities.
R2/L1
S2/L2
T2/L3
R/L11
S/L21
T/MC1
P/L+
N/L-
22 mm
2
Overall wiring length 5 m or less
P
N-
P
N-
P
N-
8 m
2
2 mm
2
8 mm
2
3.5 mm
2
2 mm
2
Junction terminal
Wire as short as possible
First unit:
22mm
2
assuming that the total
of servo amplifier capacities is
15 kW since 7 kW + 3.5 kW +
2.0 kW = 12.5 kW.
Second unit:
8mm
2
assuming that the total of
servo amplifier capacities is 7kW
since 3.5 kW + 2.0 kW = 5.5 kW.
Third unit:
2mm
2
assuming that the total of
servo amplifier capacities is 2kW
since 2.0 kW = 2.0 kW.
FR-CV-30K Servo amplifier (7 kW)
Servo amplifier (3.5 kW)
Servo amplifier (2 kW)
(Note)
(Note)
(Note)
Note. When using the servo amplifier of 7 kW or less, make sure to disconnect the wiring of built-in regenerative
resistor (5 kW or less: P and D, 7 kW to 7 kW: P and C).