11. OPTIONS AND AUXILIARY EQUIPMENT
11 - 35
11.9 Selection example of wires
POINT
To comply with the UL/CSA standard, use the wires shown in appendix 5 for
wiring. To comply with other standards, use a wire that is complied with each
standard.
Selection condition of wire size is as follows.
Construction condition: One wire is constructed in the air.
Wire length: 30 m or less
The following diagram shows the wires used for wiring. Use the wires given in this section or equivalent.
5) Power regenerative converter lead
Power regenerative
converter
N-
3) Regenerative option lead
Regenerative option
2) Control circuit power supply lead
C
P+
L1
L2
L3
L11
L21
1) Main circuit power supply lead
Power supply
Servo amplifier
U
V
W
M
4) Servo motor power supply lead
5 m or less