APPENDIX
App. - 14
App. 7.7.2 Specifications
Safety logic unit model MR-J3-D05
Voltage 24 V DC
Control circuit
power supply
Permissible
voltage fluctuation
24 V DC ± 10%
Power supply
capacity
[A] 0.5 (Note 1, 2)
Compatible
system
2 systems (A-axis, B-axis independent)
Shut-off input 4 points (2 point × 2 systems) SDI
: (source/sink compatible) (Note 3)
Shut-off
release input
2 points (1 point × 2 systems) SRES
: (source/sink compatible) (Note 3)
Feedback input 2 points (1 point × 2 systems) TOF
: (source compatible) (Note 3)
Input type Photocoupler insulation, 24 V DC (external supply), internal limited resistance 5.4 kȍ
STO
: (source compatible) (Note 3)
Shut-off output
8 points (4 point × 2 systems)
SDO
: (source/sink compatible) (Note 3)
Output type
Photocoupler insulation, open-collector type
Permissible current: 40 mA/1 output, Inrush current: 100 mA/1 output
Delay time
setting
A-axis: Select from 0 s, 1.4 s, 2.8 s, 5.6 s, 9.8 s, or 30.8 s.
B-axis: Select from 0 s, 1.4 s, 2.8 s, 9.8 s, or 30.8 s.
Accuracy: ±2%
Safety function
STO, SS1 (IEC/EN 61800-5-2)
EMG STOP
㧘
EMG OFF IEC/EN 60204-1)
Standards certified
by CB
EN ISO 13849-1 category 3 PL d, EN 61508 SIL 2, EN 62061 SIL CL 2, and EN 61800-5-2 SIL
2
Response
performance
(when delay time
is set to 0s)
10 ms or less (STO input off ĺ shut-off output off)
Test pulse input
(STO) (Note 4)
Test pulse interval: 1 Hz to 25 Hz
Test pulse off time: Up to 1 ms
Mean time to
dangerous failure
(MTTFd)
516 years
Diagnosis
converge (DC avg)
93.1%
Safety
performance
Average
probability of
dangerous failures
per hour (PFH)
4.75 × 10
-9
[1/h]
Compliance to
standards
CE marking
LVD: EN 61800-5-1
EMC: EN 61800-3
MD: EN ISO 13849-1
㧘
EN 61800-5-2
㧘
EN 62061
Structure Natural-cooling, open (IP rating: IP 00)
Ambient
temperature
0 °C to 55 °C (non-freezing), storage: -20 °C to 65 °C (non-freezing)
Ambient humidity 90% RH or less (non-condensing), storage: 90% RH or less (non-condensing)
Environment Ambience Indoors (no direct sunlight), free from corrosive gas, flammable gas, oil mist, dust, and dirt
Altitude Max. 1000 m above sea level
Vibration 5.9 m/s
2
or less at 10 Hz to 55 Hz (directions of X, Y, and Z axes)
Mass [kg] 0.2 (including CN9 and CN10 connectors)
Note 1.
2.
3.
4.
Inrush current of approximately 1.5 A flows instantaneously when turning the control circuit power supply on. Select an
appropriate capacity of power supply considering the inrush current.
Power-on duration of the safety logic unit is 100,000 times.
_: in signal name indicates a number or axis name.
This function diagnoses malfunction of contacts including an external circuit by shortly turning off signals from a controller to
the servo amplifier at a constant period while input signals of the servo amplifier are on.