3. SIGNALS AND WIRING
3 - 30
3.6 Detailed description of signals
3.6.1 Position control mode
POINT
⟎࡙࠾࠶࠻ߣࠨࡏࠕࡦࡊߩᜰࡄ࡞ࠬߩ⺰ℂࠍᰴߩࠃ߁ߦวߖߡߊߛ
ߐޕ
Q series/L series positioning module Pr. 23 setting
Command pulse logic setting
Signal type
Q series/L series positioning
module Pr. 23 setting
MR-J4-_A servo amplifier [Pr.
PA13] setting
Positive logic Positive logic (_ _ 0 _)
1) Open-collector type
Negative logic Negative logic (_ _ 1 _)
Positive logic (Note) Negative logic (_ _ 1 _)
(differential line driver)
Positive logic (Note) Positive logic (_ _ 0 _)
Note.
For Q series and L series, the logic means N-side waveform. Therefore, reverse the input
pulse logic of the servo amplifier.
F series Positioning module
Command pulse logic setting
Signal type
F series Positioning module
(fixed)
MR-J4-_A servo amplifier [Pr.
PA13] setting
Open-collector type
Differential line driver type
Negative logic Negative logic (_ _ 1 _)
(1) Pulse train input
(a) Input pulse waveform selection
You can input command pulses in any of three different forms, and can choose positive or negative
logic. Set the command pulse train form in [Pr. PA13]. Refer to section 5.2.1 for details.
(b) Connection and waveform
1) Open-collector type
Connect as follows.
⚂1.2k䕑
⚂1.2k䕑
SD
ࠨࡏࠕࡦࡊ
OPC
PP
NP
DOCOM
DC24V
(ᵈ)
Note. Pulse train input interface is comprised of a photocoupler.
Therefore, it may malfunction since a current is reduced when connect a resistance
to a pulse train signal line.
24 V DC
Adjust the logic of a positioning module and command pulse as follows.
Open-collector type
Differential line driver type
Servo amplifier
pproximately
(Note)
pproximately