APP - 11 
APPENDICES 
 
APPENDIX 1.4 Drive module errors 
Table 1.2 Drive module error (100 to 1199) list 
Control mode of virtual servo axis 
Error 
class 
Error 
code 
Positioning 
Fixed-pitch feed 
Speed 
Speed switching 
Constant-speed 
JOG 
Manual pulse generator 
Synchronous encoder 
Position follow-up 
Error cause 
Error 
processing 
Corrective action 
100 
           
 
 
• The PLC ready flag (M2000) or 
PCPU READY complete flag 
(SM500) is OFF. 
• Set the Motion CPU to RUN. 
• Turn the PLC ready flag 
(M2000) on. 
101 
           
 
 
• The start accept flag (M2001 to 
M2032) for applicable axis is ON. 
• Take an interlock in the 
program not to start the starting 
axis. (Use the start accept flag 
OFF of the applicable axis as 
the starting condition). 
103 
           
 
 
• The stop command (M4800+20n) 
for applicable axis is ON. 
• Turn the stop command 
(M4800+20n) off and start. 
104 
           
 
 
• The rapid stop command 
(M4801+20n) for applicable axis is 
ON. 
• Turn the rapid stop command 
(M4801+20n) off and start. 
105 
(Note) 
 
 
 
 
 
• The feed current value is outside 
the range of stroke limit at the start. 
• Set within the stroke limit range 
by the JOG operation. 
• Set within the stroke limit range 
by the home position return or 
current value change. 
106 
(Note)
 
   
 
 
 
 
• Positioning is outside the range of 
stroke limit. 
• Perform the positioning within 
the range of stroke limit. 
• The address that does not generate 
an arc is set at auxiliary point-
specified circular interpolation or 
auxiliary point-specified helical 
interpolation. 
(Relationship between the start 
point, auxiliary point and end point.)
• Correct the addresses of the 
servo program. 
• The auxiliary point-specified circular 
interpolation or auxiliary point-
specified helical interpolation was 
started in the control unit degree 
axis which is "stroke limit invalid". 
• Make the stroke limit valid for 
the control unit degree axis 
starts the auxiliary point-
specified circular interpolation or 
auxiliary point-specified helical 
interpolation. 
Minor 
error 
107 
(Note)
 
 
 
 
• The auxiliary point-specified circular 
interpolation or auxiliary point-
specified helical interpolation was 
started in the axis which is "stroke 
limit invalid". 
Positioning 
control does 
not start. 
• Make the stroke limit valid for 
the axis starts the auxiliary 
point-specified circular 
interpolation or auxiliary point-
specified helical interpolation. 
(Note): This error code is stored at all relevant interpolation axis storage areas at the interpolation operation.