EasyManua.ls Logo

Mitsubishi Electric Q06HCPU - Page 374

Mitsubishi Electric Q06HCPU
720 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
372
3301
[SP. PARA ERROR]
The refresh setting of the intelligent function
module exceeded the file register capacity.
The intelligent function module set in GX
Configurator differs from the actually mounted
module.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
*1
Diagnostic timing
When an END instruction or a COM instruction
executed
Change the file register file for the one that
the entire target range can be refreshed.
Check the parameter setting.
Check the auto refresh setting.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
Qn(H)
QnPH
QnPRH
QnU
LCPU
[SP. PARA ERROR]
The intelligent function module's refresh
parameter setting is outside the available range.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
*1
Diagnostic timing
When an END instruction or a COM instruction
executed
Check the parameter setting.
Check the auto refresh setting.
QCPU
LCPU
[SP. PARA ERROR]
The setting of the refresh parameter range
crosses over the boundary between the internal
user device and the extended data register (D) or
extended link register (W).
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
*1
Diagnostic timing
When an END instruction or a COM instruction
executed
Set the refresh parameter range so that it
does not cross over the boundary between
the internal user device and the extended
data register (D) or extended link register (W).
QnU
LCPU
3302
[SP. PARA ERROR]
The intelligent function module's refresh
parameter are abnormal.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
*1
Diagnostic timing
At power-on/At reset/STOP RUN
Check the parameter setting.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QCPU
LCPU
3303
[SP. PARA ERROR]
In a multiple CPU system, the automatic refresh
setting or other parameter setting was made to the
intelligent function module under control of
another station.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
Delete the automatic refresh setting or
other parameter setting of the intelligent
function module under control of another
CPU.
Change the setting to the automatic refresh
setting or other parameter setting of the
intelligent function module under control of
the host CPU.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00/Q01
Qn(H)
QnPH
QnU
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU

Table of Contents

Related product manuals