144
*1 When a cable is connected to the USB connector at all times, clamp the cable to prevent a poor connection, moving, and
disconnection by unintentional pulling.
*2 Operate the RUN/STOP/RESET switch with your fingertips. To prevent the switch from being damaged, do not use any
tool such as screw driver.
13)
RUN/STOP/RESET switch
*2
RUN: Executes sequence program operation.
STOP: Stops sequence program operation.
RESET:
Performs hardware reset, operation error reset, operation initialization or like.
(
Page 182, Section 6.4.1)
14) Module fixing screw hole Hole for the screw used to secure to the base unit. (M3 × 12 screw)
15) Module fixing projection Projection used to secure the module to the base unit.
16) Battery connector pin
For connection of battery lead wires.
(Lead wires are disconnected from the connector when shipping to prevent the battery from
consuming.)
17) Battery Backup battery for use of standard RAM and backup power time function.
18) Module mounting lever Lever used to mount the module to the base unit.
19) Ethernet connector Connector for connecting an Ethernet device (RJ45 connector)
20) 100M LED
On: Connected at 100Mbps.
Off: Connected at 10Mbps. Or disconnected.
21) SD/RD LED
On: Data being sent/received
Off: No data being sent/received
No. Name Application