87
CHAPTER 4 INSTALLATION AND WIRING
4
4.3 Connecting an Extension Base Unit
4.3.3 Extension cable specifications
3. When plugging the extension cable to any base unit, hold the connector part of the extension
cable.
4. After fitting the extension cable, always tighten the extension cable connector fixing screws.
(Tightening torque: 0.20Nm)
(3) Disconnection of extension cable
When disconnection the extension cable, hold and pull the connector part of the extension cable after confirming
that the fixing screws have been completely removed.
4.3.3 Extension cable specifications
The extension cables are connected to transfer signals between a main base unit and an extension base unit or
between extension base units.
When the extension cables are used in combination, overall distance of the combined cable must be 13.2m or less.
Item
Type
QC05B QC06B QC12B QC30B QC50B QC100B
Cable length 0.45m 0.6m 1.2m 3.0m 5.0m 10.0m
Conductor resistance value 0.044 0.051 0.082 0.172 0.273 0.530
Weight 0.15kg 0.16kg 0.22kg 0.40kg 0.60kg 1.11kg
Main base unit
Connector
Extension cable
Flat blade screwdriver
Main base unit
Fixing screw