EasyManua.ls Logo

Mitsubishi Electric Q26UD(E)HCPU - Page 192

Mitsubishi Electric Q26UD(E)HCPU
720 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
190
*1 Flicker-OFF indicates that the output signal of the terminal turns off and on at intervals of one second for three times and
then off (opens).
*2 When using the Q61P-D in the system configured with an extension base unit, the POWER LED of the Q61P-D on the
extension base unit may turn on in dull red when the module is turned off. Note that this does not indicate an error.
The Q61P-A1 is dedicated for inputting a voltage of 100 VAC.
Do not input a voltage of 200 VAC into it or trouble may occur on the Q61P-A1.
Q64P automatically switches the input range 100/200VAC.
Therefore, it cannot be used in the intermediate voltage (133 to 169VAC).
The CPU module may not work normally if the above intermediate voltage is applied.
Individually ground the LG and FG terminals with a ground resistance of 100 or less.
When the Q61P-A1, Q61P-A2, Q61P-D, Q61P, Q62P, Q63P, Q64P or Q64PN is mounted on the extension base unit, a
system error cannot be detected by the ERR.
terminal. (The ERR. terminal is always off.)
Cables for the ERR.
contact and LIFE OUT contact must be up to 30m and installed in the control panel.
16) Power input terminals Power input terminals for Q63P and connected to a 24VDC power supply.
17) Power input terminals Power input terminals for Q64P and connected to a 100VAC/200VAC power supply.
Power supply
module
Supply power voltage
100VAC 200VAC
Q61P-A1 Operates normally. Power supply module causes trouble.
Q61P-A2
Power supply module does not cause trouble.
CPU module cannot be operated.
Operates normally.
No. Name Application

Table of Contents

Related product manuals