268
(2) Restrictions on online module change
The following operations cannot be performed during an online module change.
Issue an online module change request from multiple programming tools to one CPU module.
Write parameters to the CPU module during online module change.
The following message appears if an online module change request is issued from another programming tool to the CPU
module during online module change.
After confirming the message, select "Yes" or "No".
When "Yes" is selected
Online module change operation is switched to "Programming tool 2)" that issued the request later. (Operation is
continued from the pre-switching status.)
When "No" is selected
The operation of online module change "Programming tool 2)" requested later is suspended. (Online module change
"Programming tool 1)" executed first is continued.)
Online module change
execution canceled
Online module
change continued
Programming tool 1)Programming tool 2)
"Yes" selected
Programming tool 1)Programming tool 2)
"No" selected
Online module
change suspended
Online module change
execution continued