Appendix 1 Error Codes
Appendix 1.3 List of error codes (1000 to 1999)
1112
[TRK. CIR. ERROR]
A tracking hardware fault was detected during
running.
The tracking cable was disconnected and
reinserted without the standby system being
powered off or reset.
The tracking cable is not secured by the
connector fixing screws.
The error occurred at a startup since the
redundant system startup procedure was not
followed.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
During running
Check that the tracking cable is connected
and start up the module. If the same error
code is displayed again, the cause is a
hardware failure of the tracking cable or
CPU module. Please consult your local
Mitsubishi representative.
Confirm the redundant system startup
procedure, and execute a startup again.
For details, refer to the QnPRHCPU User's
Manual (Redundant System).
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
1113
[TRK. CIR. ERROR]
A tracking hardware fault was detected during
running.
The tracking cable was disconnected and
reinserted without the standby system being
powered off or reset.
The tracking cable is not secured by the
connector fixing screws.
The error occurred at a startup since the
redundant system startup procedure was not
followed.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
During running
Check that the tracking cable is connected
and start up the module. If the same error
code is displayed again, the cause is a
hardware failure of the tracking cable or
CPU module. Please consult your local
Mitsubishi representative.
Confirm the redundant system startup
procedure, and execute a startup again.
For details, refer to the QnPRHCPU User's
Manual (Redundant System).
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
1115
[TRK. CIR. ERROR]
A fault was detected by the initial check of the
tracking hardware.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
At power-on/At reset
The cause is a hardware failure of the CPU
module. Please consult your local Mitsubishi
representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
1116
[TRK. CIR. ERROR]
A tracking hardware fault was detected during
running.
The tracking cable was disconnected and
reinserted without the standby system being
powered off or reset.
The tracking cable is not secured by the
connector fixing screws.
The error occurred at a startup since the
redundant system startup procedure was not
followed.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
During running
Check that the tracking ca
ble is connected
and start up the module. If the same error
code is displayed again, the cause is a
hardware failure of the tracking cable or
CPU module. Please consult your local
Mitsubishi representative.
Confirm the redundant system startup
procedure, and execute a startup again.
For details, refer to the QnPRHCPU User's
Manual (Redundant System).
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
1150
[RAM ERROR]
The memory of the CPU module in the multiple
CPU high speed transmission area is faulty.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
At power-on/At reset
Take noise reduction measures.
Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of the CPU
module. Please consult your local
Mitsubishi representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnU
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU