360
3006
[PARAMETER ERROR]
The high speed interrupt is set in a Q02CPU.
The high speed interrupt is set in a multiple CPU
system.
The high speed interrupt is set when a
QA1S6B or QA6B is used.
No module is installed at the I/O address
designated by the high speed interrupt.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN/At writing to
programmable controller
Delete the setting of the Q02CPU' s high
speed interrupt. To use high speed
interrupts, change the CPU module to one
of the Q02H/Q06H/Q12H/Q25HCPU.
To use a multiple CPU system, delete the
setting of the high-speed interrupt. To use
high speed interrupts, change the system
to a single CPU system.
To use either the QA1S6B or QA6B,
delete the setting of the high speed
interrupt.
To use high speed interrupts, do not use
the QA1S6B/QA6B.
Re-examine the I/O address designated by
the high speed interrupt setting.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
[PARAMETER ERROR]
No module is installed at the I/O address
designated by the high speed interrupt or the I/O
address is outside the range.
The CPU device setting for high speed buffer
transfer is outside the range.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN/At writing to
programmable controller
Re-examine the I/O address designated by
the high speed interrupt setting.
Re-examine the buffer range designated by
the high speed interrupt setting.
QnUDV
3007
[PARAMETER ERROR]
The parameter file in the drive specified as valid
parameter drive by the DIP switches is
inapplicable for the CPU module.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN/At writing to
programmable controller
Create parameters using the programming
tool and write them to the drive specified as a
parameter-valid drive by the DIP switches.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
3009
[PARAMETER ERROR]
In a multiple CPU system, the modules for AnS, A,
Q2AS and QnA have been set to multiple control
CPUs.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset
Re-set
the parameter I/O assignment to
control them under one CPU module.
(Change the parameters of all CPUs in the
multiple CPU system.)
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnU
3010
[PARAMETER ERROR]
The parameter-set number of CPU modules differs
from the actual number in a multiple CPU system.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN/At writing to
programmable controller
The number of CPU modules in the multiple
CPU system must be the same as the value
derived as follows: (the number of CPU
modules set in the multiple CPU setting) -
(the number of PLC (empty) slots set in the
I/O assignment).
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
3012
[PARAMETER ERROR]
Multiple CPU setting or control CPU setting differs
from that of the reference CPU settings in a
multiple CPU system.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN/At writing to
programmable controller
Match the multiple CPU setting or control
CPU setting in the PLC parameter with that of
the reference CPU (CPU No.1) settings.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00/Q01
Qn(H)
QnU
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU