368
3102
[LINK PARA. ERROR]
Pairing setting in CC-Link IE Controller Network
modules installed in CPUs except for redundant
CPUs was performed.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
Examine the pairing setting for the network
parameter in the control station.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
Qn(H)
QnPH
QnU
[LINK PARA. ERROR]
A CC-Link IE module with a version that does not
support items set in the network parameter is
mounted/connected.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
Correct and write the network parameters.
Mount/connect a CC-Link IE module with a
version that supports items set in the
network parameter.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnU
[LINK PARA. ERROR]
LB/LW own station send range at LB/LW4000 or
later was set.
LB/LW setting (2) was performed.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
Correct the network range assignments of the
network parameter for the control station.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
3103
[LINK PARA. ERROR]
In a multiple CPU system, Ethernet interface
module under control of another station is
specified to the start I/O number of the Ethernet
network parameter.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
Delete the Ethernet network parameter of
Ethernet interface module under control of
another station.
Change the setting to the start I/O number
of Ethernet interface module under control
of the host station.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00/Q01
Qn(H)
QnPH
QnU
[LINK PARA. ERROR]
Although the number of modules has been set
to one or greater number in the Ethernet module
count parameter setting, the number of actually
mounted module is zero.
The start I/O No. of the Ethernet network
parameter differs from the I/O No. of the actually
mounted module.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
Correct and write the network parameters.
If an error occurs again even after it is
corrected, the cause is a hardware failure.
Please consult your local Mitsubishi
representative.
QCPU
LCPU
[LINK PARA. ERROR]
In the redundant system, although "Ethernet
(Main base)" is selected for Network type, the
Ethernet module is mounted on the extension
base unit.
In the redundant system, although "Ethernet
(Extension base)" is selected for Network type,
the Ethernet module is mounted on the main
base unit.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
QnPRH
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU