370
3105
[LINK PARA. ERROR]
CC-Link module whose station type is set to
"master station (compatible with redundant
function)" is mounted on the extension base unit
in the redundant system.
CC-Link module whose station type is set to
"master station (extension base)" is mounted on
the main base unit in the redundant system.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
Correct and write the network parameters.
If an error occurs again even after it is
corrected, the cause is a hardware failure.
Please consult your local Mitsubishi
representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
3106
[LINK PARA. ERROR]
The CC-Link link refresh range exceeded the file
register capacity.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN/When an
END instruction or a COM instruction executed
Change the file register file for the one that
the entire target range can be refreshed.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
QnPRH
QnU
LCPU
[LINK PARA. ERROR]
The network refresh parameter for CC-Link is out
of range.
Collateral information
Common information: File name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN/When an
END instruction or a COM instruction executed
Check the parameter setting.
QCPU
LCPU
[LINK PARA. ERROR]
The setting of the network refresh range crosses
over the boundary between the internal user
device and the extended data register (D) or
extended link register (W).
Collateral information
Common information: File name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
Set the network refresh range so that it does
not cross over the boundary between the
internal user device and the extended data
register (D) or extended link register (W).
QnU
LCPU
3107
[LINK PARA. ERROR]
The CC-Link parameter setting is incorrect.
The set mode is not allowed for the version of
the mounted CC-Link module.
Collateral information
Common information: File name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
Check the parameter setting.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QCPU
LCPU
3
150
[LINK PARA. ERROR]
When the CC-Link IE Field Network is used, the
network number set in "Network Parameter" and
"Switch Setting" is duplicated.
No "Network Parameter" and "Switch Setting"
are configured, or the CC-Link IE Field Network
module with an incorrect switch setting is
mounted.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset
Check the parameter setting.
Configure "Network Parameter" and
"Switch Setting", and then write network
parameters and the switch setting to the
module.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnU
LCPU
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU