396
6101
[TRK. TRANS. ERR.]
A timeout error occurred in tracking (data
transmission). (This error may be caused by
tracking cable removal or other system power-
off (including reset).)
The error occurred at a startup since the
redundant system startup procedure was not
followed.
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
Common information: Tracking transmission
data classification
Individual information: -
Diagnostic timing
Always
Check the CPU module or tracking cable. If
the same error occurs, the cause is a
failure of the CPU module or tracking cable.
Please consult your local Mitsubishi
representative.
Confirm the redundant system startup
procedure, and execute a startup again.
RUN: On
ERR.:On
CPU Status:Continue
QnPRH
6102
[TRK. TRANS. ERR.]
A data sum value error occurred in tracking (data
reception). (This can be detected from the control
system or standby system of the redundant
system.)
Collateral information
Common information: -
Individual information: -
Diagnostic timing
Always
Check the CPU module or tracking cable. If
the same error occurs, the cause is a
failure of the CPU module or tracking cable.
Please consult your local Mitsubishi
representative.
Confirm the redundant system startup
procedure, and execute a startup again.
RUN: On
ERR.:On
CPU Status:Continue
QnPRH
6103
[TRK. TRANS. ERR.]
A data error (other than sum value error)
occurred in tracking (data reception). (This error
may be caused by tracking cable removal or
other system power-off (including reset).)
The error occurred at a startup since the
redundant system startup procedure was not
followed.
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
Common information: -
Individual information: -
Diagnostic timing
Always
Check the CPU module or tracking cable. If
the same error occurs, the cause is a
failure of the CPU module or tracking cable.
Please consult your local Mitsubishi
representative.
Confirm the redundant system startup
procedure, and execute a startup again.
RUN: On
ERR.:On
CPU Status:Continue
QnPRH
6105
[TRK. TRANS. ERR.]
An error (e.g. retry limit exceeded) occurred in
tracking (data transmission). (This error may be
caused by tracking cable removal or other
system power-off (including reset).)
The error occurred at a startup since the
redundant system startup procedure was not
followed.
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
Common information: Tracking transmission
data classification
Individual information: -
Diagnostic timing
Always
Check the CPU module or tracking cable. If
the same error occurs, the cause is a
failure of the CPU module or tracking cable.
Please consult your local Mitsubishi
representative.
Confirm the redundant system startup
procedure, and execute a startup again.
RUN: On
ERR.:On
CPU S
tatus:Continue
QnPRH
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU

Table of Contents